2-port-direct-acting-normally-open-solen

Electropneumatic Positioner

Model: Rtx-1000
Type: Rotary/ Linear
Operation: Single / Double Acting
Supply Pressure : 0.3 bar above actuator requirement (minimum 1.4 bar and maximum 7 bar)
Input Signal: 4 to 20 mA DC constant current with maximum 30 VDC
Stroke: 10-150 mm 0-90°
Air Connection: 1/4″ BSP / NPT
Explosion Proof: ATEX
Protection: IP 66
Cam: Equal / Square / Square Root
Ambient Temperature: -40 °C to +120 °C
Linearity: ± 1% ± 2% ± 1% ± 2%
Hysteresis: ± 1% ± 1% ± 1% ± 1%
Sensitivity: ± 0.2% ± 0.5% ± 0.5% ± 0.5%
Repeatability: ± 0.5% ± 0.5% ± 0.5% ± 0.5%
Internal Bleeding: 3 lpm (supply pressure 1.4 kgf / cm2), 11 lpm (supply pressure 4.0 kgf / cm2)
Flow Capacity: 80 lpm (supply pressure 1.4 kgf / cm2), 200 lpm (supply pressure 4.0 kgf / cm2)
Material: Aluminium Die Casting

2-port-direct-acting-normally-open-solen

Pneumatic Positioner

MODEL: RTX-1300
Type: Linear
Operation: Single Acting Double Acting
Supply Pressure: 1.4-8.0 kgf / cm2 (20 -120 psi)
Input Signal Pressure: 0.2-1 kgf / cm2 (3-15 psi)
Stroke: 10-900 mm
Air Connection: 1/4″ BSP / NPT
Explosion Proof: Not Applicable
Protection: IP 55
Cam: Equal / Square / Square Root
Ambient Temperature: -40 °C to +120 °C
Linearity: ± 1% ± 2%
Hysteresis: ± 1% ± 1%
Sensitivity: ± 0.2% ± 0.5%
Repeatability: ± 0.5% ± 0.5%
Internal Bleeding: 10 lpm (supply pressure 1.4 kgf / cm2),
14 lpm (supply pressure 4.0 kgf / cm2)
Flow Capacity: 120 lpm (supply pressure 1.4 kgf / cm2),
300 lpm (supply pressure 4.0 kgf / cm2)

2-port-direct-acting-normally-open-solen

Pneumatic Positioner

Model: Rtx-1200
Type: Linear / Rotary
Operation: Single Acting Double Acting Single Acting Double Acting
Supply Pressure: 1.4-8.0 kgf / cm2 (20 -120 psi)
Input Signal: 0.2-1 kgf / cm2 (3-15 psi)
Stroke: 10-150 mm 0-90°
Air Connection: 1/4″ BSP / NPT
Explosion Proof: Not Applicable
Protection: IP 66
Cam: Equal / Square / Square Root
Ambient Temperature -40 °C to +120 °C, see ordering code
Linearity: ± 1% ± 2% ± 2% ± 2%
Hysteresis: ± 1% ± 1% ± 1% ± 1%
Sensitivity: ± 0.2% ± 0.5% ± 0.5% ± 0.5%
Repeatability: ± 0.5% ± 0.5% ± 0.5% ± 0.5%
Internal Bleeding: 3 lpm (supply pressure 1.4 kgf / cm2), 11 lpm (supply pressure 4.0 kgf / cm2)
Flow Capacity: 80 lpm(supply pressure 1.4 kgf / cm2), 200 lpm (supply pressure 4.0 kgf /cm2)
Material: Aluminium Die Casting

2-port-direct-acting-normally-open-solen

Position Transmitter

Type: Weatherproof/ Flameproof
Field Calibration: Auto calibration with stroke settings
Custom Set Point: 21 freely configurable set points
Position Sensing: Contactless
Indication: LCD display – Current (mA) and Position (%)
Setup: Push button on device
Conduit Entry: ½” NPT (F) or M20
Temperature: -20 °C to +60 °C (Standard) -40 C to +80 °C
General "Loop powered, no external power supply required.
External 24V DC option available.
Blind mount
Suitable for rotary and linear valves
Actuator connections in accordance with VDI/VDE 3845 and IEC 60534-6 standards.
Extensive selection of mounting kits for various kind of actuators"

2-port-direct-acting-normally-open-solen

Smart Positioners

Action: Double or single acting
Fail Safe: Failsafe or Stay-put (Fail freeze)
Linear: 0 position can start anywhere, 3 to 200 mm stroke, other strokes on request
Rotary: 0° can start anywhere, max. 359°
Measurement range: 0 to 359° with freely rotating contactless feedback shaft.
Measurement range: 0 to 300 seconds (configurable in incremental steps of 60 Seconds)
Actuator travel limit: Freely configurable in 0% to 100%
Deadband time limit: 0 to 300 seconds (freely configurable, monitoring parameter until deviations reaches within deadband)
Supply pressure: 1.4 to 8 bar / 0 to 114 psi (10 bar on request)